Turn on and test the new EDI-120 Retrofit System
Connect (turn on) the power supply to the EDI Mark VII dimmer rack.
Verify the operation of the system status LED indicators, LCD display
and programming switches.
Refer to the programming section of this manual for system
conguration.
Test the system thoroughly to ensure all wiring terminations are
functioning.
Verify all of the dimmer control outputs have the correct phase
referencing. If a dimmer control output is patched to the incorrect phase
reference, the dimmer will not dim correctly and will go to full output at
around 1% DMX input. The factory conguration for EDI-120 retrot
systems is for 3-phase applications, with the dimmer phase reference
patch set at AABBCCAABBCC... For true single-phase applications
with the phases 180° out of phase from each other, set the default
(DEFAULT) menu phase patch to phase patch 2 (ØPATCH2). The
phase patch (Ø-PATCH) menu must be used to congure non-standard
applications or for single-phase applications with the phases 120° out of
phase from each other.
Verify the fan blower is operating properly. The fan blower should turn
on with between 6-7% DMX or analog control - when DMX or analog
control drops below 6-7%, there is a 5 minute timeout on the fan blower
blower to ensure the dimmers have been cooled sufciently.